Rockwell Automation 1606-XLS240-UPSC DC Power Supply User Manual

1606-XLS240-UPSC DC-UPS Instruction Manual / DC-UPS Operating Instructions

EMC Electromagnetic Compatibility

These devices are suitable for applications in industrial environment as well as in residential,
commercial and light industry environment. These devices comply with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation. CE mark is in conformance with EMC directive 89/336 / EC,
93/68 / EC and 2004/108 / EC and the low-voltage directive (LVD) 73/23 / EC, 93/68 / EC, 2006/95 / EC.
EMC Immunity: EN 61000-6-1, EN 61000-6-2
EMC emission:
EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B

EMC electromagnetic compatibility

These devices meet the requirements for applications in both industrial environments
as well as for the residential, business and commercial sector.
The devices also meet the requirements of FCC Part 15.
The CE mark is attached and declares compliance with the EMC guidelines 89/336 / EC,
93/68 / EG, 2004/108 / EG and the low voltage directives 73/23 / EG, 93/68 / EG, 2006/95 / EG.
EMC immunity:

EN 61000-6-1, EN 61000-6-2

EMC emission: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B

User interface

A power

port

Quick-connect spring-clamp terminals for input voltage and output

voltage.

B signal port

Plug connector, inserted from the bottom. Connections for the

Ready, Buffering, Replace Battery relay contacts and for the Inhibit
input.

C Green Status LED (see Fig. 1 for LED pattern)

Ready:

Battery is charged, no wiring failure is recognized, input

voltage is sufficient and inhibit signal is not active.

Charging: Battery is charging and the battery capacity is below

85%.

Buffering: Unit is in buffer mode.

D Yellow Diagnosis LED (see Fig. 2 for LED pattern)

Overload:

Output has switched off due to long overload in buffer

mode or due to high temperature.

Replace

battery:

Indicates a battery which failed the battery quality

test (SoH test). Battery should be replaced soon.

Buffer time

expired:

Output has switched off due to setting of

Buffer-timer limiter. This signal will be displayed for 15 minutes.

Inhibit

active:

Indicates that buffering is disabled due to an active

inhibit signal.

E Red Check Wiring LED

This LED indicates a failure in the wiring, battery, battery fuse or
installation (e.g. too low input voltage).

F buffer time

Limiter

This dial limits the maximum buffer time during a buffer event to
save the battery energy, for a faster recharge and to expand the
battery life.

User interface

A power connections

Spring-loaded terminals for the input and output voltage.

B signal connections

Plug-in connector can be inserted from below. Connections for the Ready,
Buffering, replace battery relay contacts and for the inhibit input.

C Green "Status" LED (The flashing pattern is explained in Figure 1)

Ready: The DC UPS is ready for buffering. Battery is charged, no inhibit
Signal, no wiring error, input voltage is sufficient.

Charging: The battery is being charged and has a state of charge of
less than 85%.

Buffering: The DC UPS is in buffer mode.

D Yellow "Diagnosis" LED (The flashing pattern is explained in Figure 2)

Overload: Reports a deactivated output due to
Overload during buffer operation or overtemperature.

Replace battery: Reports when the battery fails the quality test
consists. Battery should be replaced as soon as possible.

Buffer-time expired: Reports a switched off output,
due to expired buffer time (buffer time limiter).

The

The message is saved and displayed for 15 minutes.

Inhibit active: An active inhibit signal prevents buffering.

E Red "Check Wiring" LED

Reports a necessary check of the wiring between the DC
UPS and battery as well as a necessary check of the battery
itself. Also reports if the input voltage is too low.

F “Buffer-time

Limiter ”

With this setting regulator, the buffer time can be limited by
To conserve the battery and to achieve a faster recharge.

Ready (1-2)

Buffering (2-3)

Replace Battery (5-6)

Inhibit (7-8)

Contact is closed when battery is charged and unit is ready to buffer.
Contact is closed when unit is buffering.
Contact is closed when a replacement of the battery is necessary.
Buffering is disabled when a voltage> 10V is applied to the pins.
Relay contact rating: max. 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A
resistive load; min.1mA at 5Vdc; 500 Vac insulated to the power port.

Contact is closed when the DC UPS is charged and ready for buffering.
Contact is closed when the device is in buffer mode.
Contact is closed when the battery needs to be replaced.
If a voltage> 10V is applied, buffering is not possible.
Load capacity of the relay contacts: max. 60Vdc 0.3A, 30Vdc 1A, 30Vac
0.5A resistive load; min.1mA at 5Vdc; isolated with 500Vac.

Fig. 1 / Fig. 1

Fig. 2 / Fig. 2

Fig. 3 / Fig. 3

Ready

Charging

Buffering

ON
OFF

ON
OFF

ON
OFF

Overload

Replace

Battery

Buffer time

expired

Inhibit

active

ON
OFF

ON
OFF

ON
OFF

ON
OFF

Wiring diagram / connection diagram 1606-XLS240-UPSC

24V

unbuffered

branch

24V

power

supply

+

-

N

L PE

DC-UPS

24V

IN

+

-

+

-

24V

buffered

branch

24V

OUT

Buffered

load

+

-

Unbuffered

load

+

-

Dimensions

Functional diagram

DC-UPS control unit with integrated battery

Battery charger

&

Tester

Cut-off

Relay

24V

power

Supply

Input

-

+

Reverse

Polarity

Protection

Input fuse

&

*

(5)

(6)

Ready

Contact

(1)

(2)

Buffering

Contact

(3)

(4)

Electronic

Current

Limiter

Buffered

Load

+

-

output

Controller

Diagnosis LED (yellow)

Check wiring LED (red)

Status LED (green)

Buffer-time limiter

10s, 30s, 1m, 3m, 10m,

Inhibit -

Inhibit +

Replace

Battery

Contact

Step up

Converter

(7)
(8)

12V 5Ah battery

+

-

Fuse

* Return current protection: This feature utilizes a MOSFET instead of a diode to minimize power losses.

PN-22662

PU-357.010.39-10A